Planning tool IPS distributors - guided configuration

Guided configuration

Create IPS
Examples of bed areas:
Intensive care Unit (ICU)
Intermediate care station (IMCU)
Premature infant room
Recovery room

Examples for surgery areas:
Operating theatre (OT)
Cardiac catheter room
Shock room
Demand determination
Based on DIN VDE 0100-710:2002-11, experience has shown that the performance per bed should be assumed to be at least 1.1 kVA.
If you do not have any values for the required power per OT, it is recommended to assume a power of 6.3kVA per OT.
With one circuit per bed, the tool provides the supply from a single IT network. From two circuits per bed, the supply from two IT networks is required for single fault protection (DIN VDE 0100-710:2012-10).
According to DIN VDE 0100-710:2012-10, one OR must be supplied from at least two different IT systems.
Attention, a socket for the connection of ME devices or ME systems allows a maximum power output of 3.68kVA!
Optimal would be electrical circuits.
Transformer definition
ECO transformers have a lower inrush current, which is why the upstream output fuse and thus also the cross-section of the supply line can be reduced for the same power. ECO transformers also have lower power dissipation.
The back-up fuse of the respective supply line limits the selectable power of the isolating transformer. Please note that the rated current of the back-up fuse must not exceed the current carrying capacity of the respective supply line.
Distributor equipment
The automatic switching device (according to DIN VDE 0100-710:2012-10) is a mandatory component of IPS distributors and can not be omitted.
The IFS is an optional extension of the insulation monitoring and serves for the automatic detection of the faulty single circuit. Without IFS, the manual search for the iso fault can be very time-consuming.
The use of a bypass function is made possible by the feed load disconnectors.
The supply line is switched directly to the transformer, thereby bridging the changeover device.
As switch: Bypass line permanently defined, fewer outgoing circuits
As terminal: Bypass line freely selectable, no loss of space.
Switch cabinet definition
The cabinet height influences the number of available outlets.
Systems to be distributed: /
Switch cabinet with one IPS
Switch cabinet with two IPS
Switch cabinet with three IPS
Overall width:
Distributor number:
Concluding overview
The following distribution lists were configured on the basis of your data - IPS were planned.
S-IPSD-IPST-IPS
Dimensions (W x D)350 x 400 mm600 x 400 mm850 x 400 mm
Height
Individual weight
Radiating heat per distributor
Number of distributor
Overall width of IPS
Colour
Supply line / outletstop / top
Required circuit breakers
Expanded reserve
Seat reserve
Transformer power
Design of transformers
Pre-fuse of the feeding distributor
Note: For outgoing circuits of the IPS, only B10 miniature circuit breakers can be used.

History

Project name: ...

Motor-driven switch-disconnectors, 2-pole

 

In combination with the UEI 710 changeover and monitoring device, the motor-driven switch-disconnectors form the automatic changeover in accordance with DIN VDE 0100-710 (VDE 0100 Part 710). The switch-disconnectors meet the criteria of reliable disconnection.

The switch-disconnectors are electrically interlocked so that it is prevented that both supply lines are connected unsynchronized.

Change-over and monitoring device UEI 710

 

The UEI-710-V.5 is a multifunctional switching and monitoring device for IPS according to DIN VDE 0100-710 (VDE 0100 Part 710) or IEC 60364-7-710 in medical applications.

Monitoring:

  • Insulation resistance
  • Load current of the isolating transformer
  • Temperature of the isolating transformer
  • Line 1 (supply line)
  • Line 2 (supply line)
  • Line 3 (line to transformer)
  • Test leads (incl. wire break monitoring)

All operating or fault messages are indicated via LEDs and full graphic display. Two integrated digital outputs and external coupling relays allow connection to the building management system (BMS).

Insulation fault detection system:
In conjunction with insulation fault detectors (e.g. IFS-710-W6), the UEI-710-V.5 represents a complete insulation fault detection system. The UEI-710-V.5 controls the insulation fault search (with integrated test current generator) and outputs output circuit-related fault messages.

Automatic switch-over:
In conjunction with motor-driven switch-disconnectors, the UEI-710-V.5 is an automatic switch-over and monitoring device in accordance with the German regulations:

  • DIN VDE 0100-710 (VDE 0100 part 710),
  • IEC 60364-7-710 and
  • ÖVE/ÖNORM E 8007

The switching between the supply lines of the general and the safe power supply (AV / SV) or the battery-supported and the safe power supply (BSV / SV) takes place within 0.5 seconds.

Miniature circuit breakers

 

2-pole miniature circuit breakers to protect the output circuits against overload and short-circuit in accordance with DIN VDE 0100-430 and DIN VDE 0100-530. If a second insulation fault occurs within the IPS, the miniature circuit breaker ensures fault protection (protection against indirect contact) in accordance with DIN VDE 0100-410. 16A miniature circuit breakers with B characteristic and 10kA breaking capacity are used as standard.

The following transformer sizes require the use of miniature circuit breakers with lower rated currents:
3.15 kVA: 10A miniature circuit breaker
4.00 kVA: 13A miniature circuit breaker.

Isolating transformer TRAK

 

The isolating transformers of the TRAK series meet all requirements of DIN VDE 0100-710 (VDE 0100 Part 710) for IPS in medical applications.

In isolating transformers, the secondary side is electrically isolated from the primary side. They have reinforced insulation and meet the requirements of DIN EN 61558-1 (VDE 570 Part 1) and DIN EN 61558-2-15 (VDE 0570 Part 2-15).

In order to reduce electrical interference, there is a static shield between the windings with an insulated connection leading out for connection to equipotential bonding. The corrosion protection is ensured by a complete vacuum resin impregnation. This measure also ensures low noise emission, even after long periods of operation.

General technical features:

  • EMB/EMI conditions are fulfilled
  • Primary voltage 230 V
  • Built-in temperature sensor
  • Insulated mounting brackets
  • Protection class IP00 (type open)
  • Protection class I
  • Classification of insulation: ta40/B
  • Connection type: Screw terminals

In addition to the standard version, the ECO version is also available. The ECO transformers are particularly characterised by their lower power dissipation and lower inrush current, which means that the upstream fuses and thus also the supply lines of the IPS distributors can be reduced.

Feed-in switch disconnectors

 

The UEI 710 Automatic Changeover Device can be disconnected from the two supply lines via the feed load disconnectors, without these having to be disconnected in the upstream distribution boards.

The feed load disconnectors enable a bypass function to be carried out.

Feed-in switch disconnectors

 

The UEI 710 Automatic Changeover Device can be disconnected from the two supply lines via the feed load disconnectors, without these having to be disconnected in the upstream distribution boards.

The feed load disconnectors enable a bypass function to be carried out.

Insulation fault detection system IFS-710-W6

 

The IFS-710-W6 has 6 integrated current transformers and is used to detect insulation faults in IPS. For this purpose, the IFS is installed on a DIN rail behind the circuit breakers of the outgoing feeders and thus monitors all assigned individual circuits.

Advantages

  • Fast localization of faulty circuits
  • Automatic detection during operation
  • No operating actions required
  • No time-consuming manual troubleshooting
  • Message and storage of errors
  • Communication via CAN bus
  • Possibility of connection to the building control system

 

Principle sequence of an insulation fault search:
The multifunctional changeover and monitoring device UEI-710-V.5 constantly monitors and determines the insulation resistance in the entire IPS. If the insulation resistance falls below a specified value, the search process is started by the integrated test current generator of the UEI-710-V.5. The test current generator feeds a test signal into the IPS. The insulation fault locator IFS-710-W6 uses its current transformers to detect the test signal in the faulty output circuit and reports it to the UEI-710-V.5 via CAN bus. This evaluates the fault locator and transmits the evaluation to the CAN bus. The evaluation can be output as individually configured messages on the peripheral display devices.

The information on the faulty circuit is stored in the integrated message memory and can be used for later evaluations.

Insulation fault detection system IFS-710-W6

 

The IFS-710-W6 has 6 integrated current transformers and is used to detect insulation faults in IPS. For this purpose, the IFS is installed on a DIN rail behind the circuit breakers of the outgoing feeders and thus monitors all assigned individual circuits.

Advantages

  • Fast localization of faulty circuits
  • Automatic detection during operation
  • No operating actions required
  • No time-consuming manual troubleshooting
  • Message and storage of errors
  • Communication via CAN bus
  • Possibility of connection to the building control system

 

Principle sequence of an insulation fault search:
The multifunctional changeover and monitoring device UEI-710-V.5 constantly monitors and determines the insulation resistance in the entire IPS. If the insulation resistance falls below a specified value, the search process is started by the integrated test current generator of the UEI-710-V.5. The test current generator feeds a test signal into the IPS. The insulation fault locator IFS-710-W6 uses its current transformers to detect the test signal in the faulty output circuit and reports it to the UEI-710-V.5 via CAN bus. This evaluates the fault locator and transmits the evaluation to the CAN bus. The evaluation can be output as individually configured messages on the peripheral display devices.

The information on the faulty circuit is stored in the integrated message memory and can be used for later evaluations.

Insulation fault detection system IFS-710-W6

 

The IFS-710-W6 has 6 integrated current transformers and is used to detect insulation faults in IPS. For this purpose, the IFS is installed on a DIN rail behind the circuit breakers of the outgoing feeders and thus monitors all assigned individual circuits.

Advantages

  • Fast localization of faulty circuits
  • Automatic detection during operation
  • No operating actions required
  • No time-consuming manual troubleshooting
  • Message and storage of errors
  • Communication via CAN bus
  • Possibility of connection to the building control system

 

Principle sequence of an insulation fault search:
The multifunctional changeover and monitoring device UEI-710-V.5 constantly monitors and determines the insulation resistance in the entire IPS. If the insulation resistance falls below a specified value, the search process is started by the integrated test current generator of the UEI-710-V.5. The test current generator feeds a test signal into the IPS. The insulation fault locator IFS-710-W6 uses its current transformers to detect the test signal in the faulty output circuit and reports it to the UEI-710-V.5 via CAN bus. This evaluates the fault locator and transmits the evaluation to the CAN bus. The evaluation can be output as individually configured messages on the peripheral display devices.

The information on the faulty circuit is stored in the integrated message memory and can be used for later evaluations.

Bypass switch

 

Switch for implementing the bypass function in combination with upstream feed-in switch-disconnectors. The supply line used for the bypass is defined in advance (preferred supply line). When switched on, the changeover direction is bridged and the preferred feed line supplies the IPS transformer directly.

The bypass switch is used for testing the changeover device without voltage interruption on the outgoing feeder line to be supplied and for voltage-free replacement of the devices during operation. An LED is used to indicate the switching status of the bypass switch.

If the bypass switch is used, the available space for miniature circuit breakers is reduced. There are 6 less outgoing circuits available.

Bypass terminal system

 

Bypass clamping system (3x3x35/25mm²) for the realisation of the bypass function in combination with upstream load disconnectors. The supply line used for the bypass can be selected as required (preferred or alternative supply line).

The bypass clamping system is used for testing the changeover device without voltage interruption on the outgoing feeder line to be supplied and for voltage-free replacement of the devices during operation.

The bypass clamping system does not reduce the number of outgoing circuit breakers that can be installed.